Victron MultiPlus 24V 230V 3000VA Inverter 70A Charger 50 Hz 16A Transfer Switch

Excl. Tax: £1,266.13 Incl. Tax: £1,519.36

Quick Overview

• Victron MultiPlus 24V 230V 3000VA Inverter 70A Charger 50 Hz 16A Transfer Switch
• Stock code: 401032

Only 100 left

Availability: In stock

OR

Details

Victron MultiPlus 24V 230V 3000VA Inverter 50A Charger 50 Hz 16A Transfer Switch

MultiPlus C 24/2000/50
PowerControl / PowerAssist Yes/Yes
Transfer switch (A) 16
Parallel and 3-phase operation Yes
INVERTER
Input voltage range (V DC) 19 – 33V
Output  Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1%
Cont. output power at 25 °C (VA) (3) 3000
Cont. output power at 25 °C (W) 2500
Cont. output power at 40 °C (W) 2200
Peak power (W) 6000
Maximum efficiency (%) 94
Zero-load power (W) 15
Zero load power in AES mode (W) 10
Zero load power in Search mode (W) 5
CHARGER
AC Input Input voltage range: 187-265 VAC           Input frequency: 45 – 65 Hz          Power factor: 1 
Charge voltage 'absorption' (V DC) 28.8
Charge voltage 'float' (V DC) 27.6
Storage mode (V DC) 26.4
Charge current house battery (A) (4) 70
Charge current starter battery (A) 4 (12V and 24V models only)
Battery temperature sensor Yes
GENERAL
Auxiliary output (A) (5) Yes (16A) 
Programmable relay (6) Yes
Protection (2) a-g
VE.Bus communication port For parallel and three phase operation, remote monitoring and system integration
General purpose com. port (7) Yes  (8)
Remote on-off Yes
Common Characteristics Operating temp.: -40 to +50 ?C Humidity (non condensing): max. 95
ENCLOSURE
Common Characteristics Material & Colour: aluminium (blue RAL 5012)                   Protection category: IP 21 
Battery-connection Four M8 bolts (2 plus and 2 minus connections)
230 V AC-connection

Screw terminals 13 mm2 (6 AWG)

Weight (kg) 18
Dimensions (hxwxd in mm) 362x258x218
STANDARDS
Safety EN 60335-1, EN 60335-2-29
Emission, Immunity EN55014-1, EN 55014-2, EN 61000-3-3
Automotive Directive  2004/104/EC

1) Can be adjusted to 60 HZ; 120 V 60 Hz on request
2) Protection key:
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) 230 VAC on inverter output
g) input voltage ripple too high

3) Non linear load, crest factor 3:1
4) At 25 ˚C ambient
5) Switches off when no external AC source available
6) Programmable relay that can a. o. be set for general alarm,
DC undervoltage or genset start/stop function
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
7) A. o. to communicate with a Lithium Ion battery BMS
8) Models with 16A transfer switch only (see Quattro for 50A transfer switch)